Balluff / Industrial communication
BNI00L4
BNI LH5-314-S52-R012Balluff BNI00L4 — IO-Link hubs — flexible and cost-effective signal collection. Interface: IO-Link 1.1.4. Operating voltage Ub: 18...30,2 VDC. Connection (COM 1): M12x1-Male connector, 4-pins, A-coded. Connection slots: 8x M12x1-Female connector, 5-pins, A-coded.
Technical essentials
- Interface
- IO-Link 1.1.4
- Operating voltage Ub
- 18...30,2 VDC
- Connection (COM 1)
- M12x1-Male connector, 4-pins, A-coded
- Connection slots
- 8x M12x1-Female connector, 5-pins, A-coded
- Digital outputs
- 16x PNP
- Configurable inputs/outputs
- PNP: Yes, NPN: No
Source consulted on 2026-10-19 Confirm family-level specifications for the selected variant.
| Interface | IO-Link 1.1.4 |
| Operating voltage Ub | 18...30,2 VDC |
| Connection (COM 1) | M12x1-Male connector, 4-pins, A-coded |
| Connection slots | 8x M12x1-Female connector, 5-pins, A-coded |
| Digital inputs | 16x PNP/NPN, Type 1, Type 3 |
| Digital outputs | 16x PNP |
| Configurable inputs/outputs | PNP: Yes, NPN: No |
| Expansion port | oui |
| Individual channel monitoring | oui |
| Additional function | Vibration / Internal temperature / Découverte des appareils |
| Total current US, sensor | 2 A |
| Switching current | 16x 2 A |
| Total current UA, actuator | 4 A |
| Housing material | PBT GF30 / inserts : stainless steel, 1.4404 |
| Dimensions | 68 x 38.3 x 183.5 mm |
| Ambient temperature | -25...60 °C |
| IP rating | IP67, Etat vissé |
| Transmission rate | COM3 (230,4 kbauds) |
| Minimum process data cycle | 2 ms |
| Process data IN | 12 Byte |
| Process data OUT | 2 Byte |
| Secondary features | Basic Statistics / Boot Cycle Counter / Device Discovery / Extreme Environment Status / Identification / Logic Blocks / Operating Hours Counter / Signal Delay / Signal Speed Monitor / Switching Counter / Variant Configuration / Voltage and Current Monitoring |
| Secondary features for condition monitoring | Vibration monitoring / Internal temperature monitoring / Inclination monitoring and installation aid |